| 管系名称 | 管道规格/mm | 设计参数 | 材 料 | 直径允许偏差 mm | 壁厚允许偏差 mm | ||
| 温度 ℃ | 压力 MPa | ||||||
| 主蒸汽主管 | ID368.3×83.2 | 546 | 18.3 | P22 | +3.18 -0mm | +15% 0 | |
| 17.5 | |||||||
| ID368.3×41 | 546 | 18.3 | P91 | +3.18 -0mm | +15% 0 | ||
| ID368.3×38 | 17.5 | ||||||
| 主蒸汽支管 | ID273×62.3 | 546 | 18.3 | P22 | +2.36 -0mm | +15% 0 | |
| 17.5 | |||||||
| ID273×30 | 546 | 18.3 | P91 | +2.36 -0mm | +15% 0 | ||
| ID273×28 | 17.5 | ||||||
| 高温再热蒸汽 主管 | ID635×31 ID679×34 | 546 | 4.52 | P22 | +3.96 -0mm | +22.5% 0 | |
| 4.19 | |||||||
| ID699×36 | 4.6 | ||||||
| ID635×20 ID679×20 | 546 | 4.8 | P91 | +3.96 -0mm | +22.5% 0 | ||
| 高温再热蒸汽 支管 | ID508×24.8 | 546 | 4.52 | P22 | +3.18 -0mm | +22.5% 0 | |
| 4.19 | |||||||
| ID508×27 | 4.6 | ||||||
| ID508×20 | 546 | 4.8 | P91 | +3.18 -0mm | +22.5% 0 | ||
| 低温再热蒸汽 主管 | OD813×21 OD813×17.5 | 350 | 4.6 | A672B70CL32 | ±0.5% | +1.1 -0.3 | +1.0 -0.3 |
| 343 | 4.35 | ||||||
| 低温再热蒸汽 支管 | OD559×16 OD559×14.3 | 350 | 4.6 | A672B70CL32 | ±0.5% | +0.8 -0.3mm | |
| 343 | 4.35 | ||||||
| 高压给水主管 | OD406.4×55 | 278 | 27.3 | St45.8/Ⅲ | ±1.0% | ±10% | |
| OD355.6×25 | 283 | 25.78 | 15NiCuMoNb5-6-4 | ±12.5% | |||
| 高压给水支管 | OD298.5×40 | 278 | 27.3 | St45.8/Ⅲ | ±1.0% | ±10% | |
| OD244.5×20 | 283 | 25.78 | 15NiCuMoNb5-6-4 | ±12.5% | |||
| 注1:材料P22、P91标准为ASTM A335,A672B70 CL32标准为ASTMA672,A106B标准为ASTMA106,St45.8Ⅲ标准为DIN17175,15NiCuMoNb5-6-4标准为EN10216-2。外径管的直径与壁厚允许偏差与相应的钢管标准要求一致。 注2:管道为内径管时,直径允许偏差是指内径允许偏差;管道为外径管时,直径允许偏差为外径允许偏差。 注3:直径允许偏差用百分数表示时,其极限偏差值等于规定外径乘以该百分数:壁厚允许偏差用百分数表示时,其极限偏差值等于规定壁厚乘以该百分数。 | |||||||
| a:对锻制与镗孔管,钢管壁厚上极限偏差为3.2mm,下极限偏差为0. b:当设计另有规定时,内径控制管的壁厚上极限偏差应符合设计要求。 c:低温再热蒸汽管道OD813×21的壁厚上极限偏差为+1.1mm,OD813×17.5的壁厚上极限偏差为+1.0mn;低温再热蒸汽管道局部壁厚上偏差值允许达到表中规定值的1.75倍。 d:对于高压给水管道,当外径D₀ ≥355.6mm且t₀/D₀ >0.10时,允许局部壁厚超过上极限偏差值,超过部分允许达到规定壁厚的5%;当外径D₀ ≤219.1mm时,壁厚允许偏差取±12.5%tn和±0.4mm两者中的较大值。 | |||||||