| 管系名称 | 管道规格 mm | 设计参数 | 材 料 | 直径允许偏差 mm | 壁厚允许偏差 mm | |
| 温度 ℃ | 压力 MPa | |||||
| 主蒸汽主管 | ID368×92 | 610 | 27.46 | P92 | +3.18 0 | +15% 0 |
| ID356×94 | 610 | 28.84 | ||||
| 主蒸汽支管 | ID260×66 | 610 | 27.46 | P92 | +2.36 0 | +15% 0 |
| ID254×68 | 610 | 28.84 | ||||
| 高温再热蒸汽 支管 | ID749×38 | 608 | 6.0 | P92 | +3.96 0 | +22.5% 0 |
| ID686×42 | 608 | 7.3 | +15% 0 | |||
| 高温再热蒸汽 支管 | ID527×28 | 608 | 6.0 | P92 | +3.18 0 | +15% 0 |
| ID495×31 | 608 | 7.3 | ||||
| 低温再热蒸汽 主管 | OD1219×38 | 385 | 6.0 | A672B70CL32 | ±0.5% | +2.7 -0.3 |
| OD1168×47 | 400 | 7.3 | +3.3 -0.3 | |||
| OD1219×38 | 425 | 6.0 | A6911-1/4CrCL22 | ±0.5% | +2.7 -0.3 | |
| OD1168×42 | 425 | 7.3 | +3.0 -0.3 | |||
| 低温再热蒸汽 支管 | OD863.6×27 | 385 | 6.0 | A672B70CL32 | ±0.5% | +1.4 -0.3 |
| OD813×33 | 400 | 7.3 | +1.6 -0.3 | |||
| 低温再热蒸汽 支管 | OD863.6×27 | 425 | 6.0 | A6911-1/4CrCL22 | ±0.5% | +1.4 -0.3 |
| OD813×30 | 425 | 7.3 | ||||
| 高压给水主管 | OD660×65 | 302 | 36 | 15NiCuMoNb5-6-4 | ±1.0% | ±12.5% |
| OD610×65 | 302 | 38 | ±10% | |||
| 高压给水支管 | OD457×50 | 302 | 36 | 15NiCuMoNb5-6-4 | ±1.0% | ±10% |
| OD457×50 | 302 | 38 | ||||
| OD457×50 | 193 | 39 | 15NiCuMoNb5-6-4 | |||
| OD457×55 | 193 | 42 | ||||
| 注1:材料P92标准为ASTM A335,A672B70CL32标准为ASTM A672,A6911-1/4CrCL22标准为ASTM A691,15NiCuMoNb5-6-4标准为EN10216-2。外径管的直径与壁厚允许偏差与相应的钢管标准要求一致。 注2:管道为内径管时,直径允许偏差是指内径允许偏差;管道为外径管时,直径允许偏差为外径允许偏差。 注3:直径允许偏差用百分数表示时,其极限偏差值等于规定外径乘以该百分数;壁厚允许偏差用百分数表示时,其极限偏差值等于规定壁厚乘以该百分数。 | ||||||
| a:对锻制与镗孔管,钢管壁厚上极限偏差为3.2mm,下极限偏差为0。 b:当设计另有规定时,内径控制管的壁厚上极限偏差应符合设计要求。 c:低温再热蒸汽管道局部壁厚上偏差值允许达到表中规定值的1.75倍。 d:对于高压给水管道,当外径D₀ ≥355.6mm且t„/D。>0.10时,允许局部壁厚超过上极限偏差值,超过部分允许达到规定壁厚的5%;当外径D₀ ≤219.1mm时,壁厚允许偏差取±12.5%zn和±0.4mm两者中的较大值。 | ||||||